Technical Data - Pa Module (101-201610) - Procentec ComBricks User Manual

Profibus data hub for repeaters and fiber optics modules
Table of Contents

Advertisement

29 Technical Data - PA Module (101-201610)

Technical Data - PA Module (101-201610)
Backplane
PROFIBUS networks
Modules
Power supply for the module
Current consumption
Compatible backplane units
PROFIBUS PA power specifications
Trunk voltage
Trunk current
Current consumption
Number of devices
Baudrate
PROFIBUS PA cable specifications
Cable length
Wire diameter
Wire type
Termination
Connector specifications
2 Removable PA screw terminals
PA-, PA+
SH
I
Removable power connector
-, +
SH
PROFIBUS DP specifications
Transmission speed
Transmission speed detection
PROFBIUS busparameters
Address
Supported Protocols
Oscilloscope specifications
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
4 (set by dipswitches or web server)
Link mode: 9 modules (in the first 10 slots)
Coupler mode: 9 modules (in the first 10 slots)
Monitoring mode: 4 modules (in the first 10 slots)
Provided through the backplane
± 350 mA (555 mA max)
101-200011, 101-200012, 101-200023, 101-200024,
101-200027
10 .. 27 V (customizable and Non-Ex)
500 mA
10 mA (in all modes)
32 (PROFIBUS PA specifications)
31.25 kbps PA signal
Max. 1900 m cable length (PROFIBUS PA specifications)
< 2.5 mm2
Stranded or solid core
Automatic (ON in Link and Coupler mode)
(1-on-1)
Wire colors are undefined
Direct grounding
Indirect grounding
11 .. 28 V (Max. 600 mA)
Direct grounding
9.6 kbps .. 12 Mbps (including 45.45 kbps)
Auto detect (< 10 s detection and 50 s lost time)
No adjustments required in Link mode
NO bus address required (Link has address 1 on PA)
DP-V0, DP- V1, DP-V2, FDL, MPI, FMS, PROFIsafe, PROFIdrive
and any other FDL based protocol