4.7 Output Control

Head Stations:
1A, 1B, 1C
Firmware:
V1.254 and higher
Login:
User
With the Output Control feature the user can directly respond to an event with the onboard relay in the Head
Station or the channels from output modules in the backplane. The web server offers 10 customizable controls
that can be set to the following behavior:
Not active
Manual ON/OFF
Live toggle of the output channels
Time
Time ON and Time OFF
PROFIBUS event
Syncs, retries, bus voltage too low, redundancy failure, PA failure,
fiber optic failure etc.
System event
Redundant power change or ComBricks failures
Fig. 33 - Output Control
After power down/up, the ComBricks loads and restores these settings.
It is recommended to have a security policy concerning passwords with this feature, because the
user is able to control REAL output points.