1.7 CommDTM

The FREE ComBricks CommDTM offers FDT 1.2 based asset management tools a powerful Ethernet pass-
through to access PROFIBUS devices which are connected on ComBricks repeater modules.
The internal DP-V1 class 2 masters are able to drive 2 out of 4 networks. When a CommDTM connection is
closed, the user can enter another network. The 2 active networks are managed by 1 or 2 PC Ethernet
connections.
The CommDTM provides the same auto baudrate detection facilities as the famous ProfiCaptain. It detects all
busparameters before it goes online. An available master address is required.
CommDTM
CommDTM
Device DTM
PROFIBUS DP
Fig. 11 - CommDTM structure
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
FDT Applications
Device DTM
PROFIBUS PA
ProfiTrace OE