33 Technical Data – RS-485-IS Barrier (101-201410)
Technical Data – RS-485-IS Barrier (101-201410)
Backplane
PROFIBUS networks
Modules
Power supply
Current consumption
Compatible backplane units
Protocol specifications
Supported Protocols
Address
Transmission speed
Transmission speed detection
Data delay time (normal mode)
Data delay time (redundant mode)
Delay time jitter
Oscilloscope specifications
Frequency
Resolution
Differential range
PROFIBUS cable specifications
Cable lengths
Number of devices
Required termination
Redundancy
Dipswitches
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
4 (set by dipswitches or web server)
10 (positioned in the first 10 slots)
Provided through the backplane
± 450 mA (740 mA max)
101-200011, 101-200012, 101-200023, 101-200024,
101-200027
DP-V0, DP- V1, DP-V2, FDL, MPI, FMS, PROFIsafe, PROFIdrive
and any other FDL based protocol
No bus address required
9.6 kbps .. 1.5 Mbps (including 45.45 kbps)
Auto detect (< 10 s detection and 50 s lost time)
2.0 TBit
12.0 TBit
Max. ¼ TBit
192 MS/s
27 mV
-3.49 .. 3.49 V
1200 m at 9.6 kbps .. 93.75 kbps
1000 m at 187.5 kbps
400 m at 500 kbps
200 m at 1.5 Mbps
Maximum 31 devices per channel (busloads)
DB9-IS connector with internal 200Ω only
Yes, maximum 10 cables activated by switch