13.2.2 PROFINET LEDs

The PND-001 module has three PROFINET diagnostic LEDs: RUN, SF (System Fail) and BF (Bus Fail).
LED
State
Meaning
RUN
Off
Internal application firmware is not running (PROFINET stack).
(green)
Remedy: Update application firmware.
On
Internal application firmware is running (PROFINET stack).
SF
Off
No error
System
Fail
On
System error, or the received expected configuration (from configuration tool) does not
(red)
match the actual configuration (I/O or proxy modules in the backplane).
On
PND-001 module is not in Data Exchange with a PROFINET master.
BF
Off
PND-001 module is in Data Exchange with a PROFINET controller.
Bus Fail
(red)
Flashing
No data transfer between the PROFINET Controller and the PND-001 module, although a
(0.5 Hz)
physical link is established
Causes:
Remedy:
On
No physical link.
Remedy: check the cable and switch.
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
Incorrect device name
The PROFINET Controller is switched off
Check the configuration and assign a valid device name to the PND-001 module.
Check the PROFINET Controller.
137/219