34 Technical Data - PROFIBUS Slave Module PBS-001

Technical Data – PROFIBUS Slave PBS-001 (101-220210)
Backplane
PROFIBUS networks
Modules
Power supply
Current consumption
Compatible backplane units
Compatible partner/gateway modules
PROFIBUS DP Slave Device
Supported protocol
Ident Number
GSD filename
Bus address
Transmission speed
Transmission speed detection
Maximum transferrable data
Max. transferrable data per gateway
Maximum number of gateway modules
Selectable number of I/O bytes or
words per gateway
Consistent Gateways:
Failsafe options
Simulation input patterns
RS-485 Repeater
Bus channels
Connector
Number of devices
Cable lengths
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
10 (web server), 4 (dipswitches and web server)
10 (positioned in the first 10 slots)
Provided through the backplane
± 390 mA typical (625 mA max)
101-200011, 101-200012, 101-200023, 101-200024, 101-
200027
101-220210, 101-220110, 101-210210, 101-210110, 101-
210010
DP-V0 (certification number: Z01776)
696F
PROC696F.gsd (www.procentec.com/downloads)
1 – 99 (set by rotary switches) or
0 – 126 (set by software)
9.6 kbps .. 12 Mbps (including 45.45 kbps)
Auto detect
244 bytes input and 244 bytes output
128 bytes input and 128 bytes output
9
1, 2, 3, 4, 8, 12, 16, 20, 24, 28, 32, 64 bytes
48, 64 words
2, 3, 4, 8, 12, 16, 20, 24, 28, 32, 64 bytes
48, 64 words
Outputs OFF, Outputs ON, Keep last value, Custom failsafe
value
ON, OFF, Blink, Up counter, Down counter, Zig Zag
1 x RS-485
DB9 (A, B, 5V, GND)
Maximum 31 devices per channel (busloads)
1200 m at 9.6 kbps .. 93.75 kbps
1000 m at 187.5 kbps
400 m at 500 kbps
200 m at 1.5 Mbps
186/219