21 Technical Data - SCOPE Repeater (101-201210)

Technical Data - SCOPE Repeater (101-201210)
Backplane
PROFIBUS networks
Modules
Power supply
Current consumption
Compatible backplane units
Protocol specifications
Supported Protocols
Address
Transmission speed
Transmission speed detection
Data delay time (normal mode)
Data delay time (redundant mode)
Delay time jitter
Oscilloscope specifications
Frequency
Resolution
Differential range
PROFIBUS cable specifications
Cable lengths
Wire diameter (for the screw terminals)
Wire type
Number of devices
Termination
Cascading depth
Redundancy
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
4 (set by dipswitches or web server)
10 (positioned in the first 10 slots)
Provided through the backplane
± 400 mA (555 mA max)
101-200011, 101-200012, 101-200023, 101-200024,
101-200027
DP-V0, DP- V1, DP-V2, FDL, MPI, FMS, PROFIsafe, PROFIdrive
and any other FDL based protocol
NO bus address required
9.6 kbps .. 12 Mbps (including 45.45 kbps)
Auto detect (< 10 s detection and 50 s lost time)
2.0 TBit at 9.6 kbps .. 3 Mbps
2.75 TBit at 6 Mbps
3.75 TBit at 12 Mbps
12.0 TBit at 9.6 kbps .. 3 Mbps
12.75 TBit at 6 Mbps
13.75 TBit at 12 Mbps
Max. ¼ TBit
192 MS/s
50 mV
-6.436 .. 6.436 V
1200 m at 9.6 kbps .. 93.75 kbps
1000 m at 187.5 kbps
400 m at 500 kbps
200 m at 1.5 Mbps
100 m at 3 Mbps .. 12 Mbps
2
< 1.5 mm
Stranded or solid core
Maximum 31 devices per channel (busloads)
Integrated (switchable - PB RS-485 - 390/220/390 Ohms)
No limit, only busparameter limitation of the master
Yes, maximum 10 cables activated by switch
163/219