13.4.3 Assigning a pre-defined name

The positions 1 - 9 of the rotary switch assign a pre-defined name to the device. The name
has the format "ComBricks-x" where 'x' corresponds to the selected digit of the rotary
switch.
For example, in position 4 the module has the following device name: "ComBricks-4". The
name is read during startup of the module; changing the rotary switch during operation
does not change the device name.

13.5 Remote I/O mode

The PND-001 module can be included in a PLC project with the GSDML as any other PROFINET device. After the
module has been set up with a name, you can start configuring it in the network with the configuration tool of
the PLC. Refer to the manual of the supplier of your configuration tool for instructions for that tool.
This example, a typical ComBricks setup with remote I/O, is built up as follows (see Fig. 92).
Fig. 92 - Example configuration for Remote I/O
The first slot is occupied by the PND-001 module, and next to it are an 8DO and Relay module.
Open the PROFINET Controller configuration tool and insert/import the PND-001 GSD with filename "GSDML-
V2.25-PROCENTEC-ComBricks PND_001-20120831.xml" (download it from www.procentec.com/gsd).
Then insert the correct modules into the configuration tool. Drag the following device into the configuration:
'Head Station+PND-001(SLOT 01)'. Make sure that this slot corresponds with the physical slot of the PND-001.
See Fig. 93.
Fig. 93 - Select the device with correct slot number
nd
Next, insert the correct modules into the configuration tool. In the 2
slot place a 8DO-24V-0.5A, and the last
module is the 4RO-230V-5A.
Fig. 94 shows the complete configuration for this ComBricks system.
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
140/219