Event Configuration - Procentec ComBricks User Manual

Profibus data hub for repeaters and fiber optics modules
Table of Contents

Advertisement

The automatic triggering can generate 1000 .PTC files per network
generated, the follow-up event will delete the oldest file and replace it with the latest event. This
system secures the storage space of the SD card.
.PTC files can be opened with ProfiTrace 2.5.3 and higher (offline and no licenses required).
The file name contains the MAC address of the Head Station, the network number and the file number (0-999).

5.4 Event configuration

For generating emails and entries in the network log, the event configuration has to be set for each network.
Fig. 41 shows an example with multiple event options. Since Head Station version v1.293 it is possible to send
emails of individual events to specific email groups (see also paragraph 4.11). This is useful for large
organizations with different maintenance teams or user groups.
Paragraph 5.9 describes the events and when they occur.
Fig. 41 - Event configuration
To reduce an unwanted overload of emails or log entries, the events can be set to Off, Once or Interval.
4
This feature is available in firmware version 1.264 and higher.
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
Every network can be
configured individually
Multiple options
for an event:
-
Off
-
Once
-
Interval
4
. After 1000 files have been
Event notification: by
Event notification: by
email and/or log
email and/or log
Enable email for each
event per group
63/219

Advertisement

Table of Contents
loading

Table of Contents