Fig. 68 - Parameter assignment window
After selecting 'Failsafe value' in the drop-down list, you can enter a decimal value of 0 to 255 in the Failsafe
value box.

11.4.3 Input test patterns

The functionality in this paragraph is only available for PBS-001 modules
with software version 2.1 or higher. Please refer to paragraph 17.2 for a
guide to update your module. Use the correct GSD file.
The input modules of ComBricks can be set to a test mode. Different test patterns can be generated
automatically for testing purposes, for example during a commissioning or FAT/SAT phase, to see if the PLC is
programmed correctly.
The following simulation patterns are available:
On (all inputs to ON)
Off (all inputs to OFF)
Blinking (all inputs will blink, frequency is configurable)
Up counter (inputs will increase, frequency is configurable)
Down counter (inputs will decrease, frequency is configurable)
Zig-zag (inputs will zigzag up and down, frequency is configurable)
Open the properties of a ComBricks input module (generally by double-clicking on it) in the configuration tool
and select 'Parameter Assignment' or 'Module Parameters'. A screen similar to Fig. 69 will appear:
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
115/219