Technical Data - 6A Power Module T1 (101-230010) - Procentec ComBricks User Manual

Profibus data hub for repeaters and fiber optics modules
Table of Contents

Advertisement

Technical Data - 6A Power Module T1
36
Technical Data - 6A Power Module Type 1 (101-230010)
Backplane
Modules
Current consumption from the backplane
Compatible backplane units
Backplane power
Current
Maximum combined backplane current
Power supply
Nominal supply voltage
Current consumption
Power
Reverse polarity protection
Redundant power supply
Installation notes:
The device shall be supplied from an isolating transformer having a secondary Listed fuse rated either:
Maximum 5 amps for voltages 12 .. 20 V, or
Maximum 4 amps for voltages 21 .. 24 V, or is supplied by a Class 2 power supply, or equivalent.
When using the Power Module, remove power from the Head Station. If power redundancy is required,
use two Power Modules. When moving the Power Module to a different slot: remove power before taking
out the module.
Power supply connectors
Pins
Wire diameter (for the screw terminals)
Wire type
LEDs
ERR ON
ERR + RUN OFF
Others
Head Station firmware
Dimensions (L x W x H)
Operating temperature
Weight
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
(101-230010)
32 (all slots)
± 130 mA (465 mA max)
101-200011, 101-200012, 101-200023, 101-200024,
101-200027
6 A
12 A (provided by all inserted power modules)
12 .. 30 VDC
Max. 2 A @ 24 VDC
Max. 42 W
Yes
Yes
1 = - (left)
2 = + (middle)
3 = Ground (right)
2
< 2.5 mm
Stranded or solid core
Input voltage too low, or maximum current
No power supply connected
At least version 1.265
140 x 110 x 25 mm
0 .. 60 °C
125 g
190/219