10.3 Dipswitches

Use the DIP switches at the bottom of the module to change the behavior of the channels. The settings of these
DIP switches are only read during startup of the module. The switches have the following values:
In all ring redundancy modes, the Ring dipswitches must be switched to the LEFT position.
In case both channels are connected in line mode (to two different ComBricks FO modules),
disable the RED switch (switch to RIGHT).
In case of one line connection, disable the RED switch (switch to RIGHT) and disable the
unused fiber channel CH1 or CH2.
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
Network selection
Network 1: NW0 = Left, NW1 = Left
Network 2: NW0 = Right, NW1 = Left
Network 3: NW0 = Left, NW1 = Right
Network 4: NW0 = Right, NW1 = Right
Use dipswitches or server settings ( Left = DIP, Right = SERVER)
Enable or disable channel 1 or 2 (Left = ON, Right = OFF)
Ring Redundancy or Line (Left = RING, Right = LINE)
NU = not used