4.12.1 Backup settings to SD-Card

When this button is clicked, all customizable settings of each individual network and of the Head Station are
saved to SD-Card. These settings include Message recording settings, name and identification tags, scope
settings and IP and email settings.
This feature allows a quick and easy replacement of a defective Head Station. If a Head Station needs to be
replaced, and settings have been backed up on SD card, remove the SD card from the slot and place it in the
new Head Station. Then continue with paragraph 4.12.2.

4.12.2 Restore settings from SD-Card

When you replaced the SD card with information from another Head Station, click 'Restore settings from SD
Card' to load all information into the new Head Station. Then click 'OK' on the confirmation window.
Settings are loaded and activated instantly; no restart is required.

4.12.3 Restore settings to factory defaults

This button clears all entered information and restores the ComBricks Head Station to the default factory
values. The new IP address is 192.168.1.254

4.12.4 Clear all data

When a ComBricks set has been installed and is ready for normal operation, it may have recorded several
events which are not 'real' faults. This can happen during wiring or commissioning phase. Press 'Clear all data'
to start the ComBricks logging and recording functions with a clear memory. Then click 'OK' on the
confirmation window.
IMPORTANT NOTE: This will also clear all Message Recording files!

4.12.5 Restart the device

To restart the device, for example to let it read new dipswitch settings or DNS server settings, click the 'Restart
the device' button. Then click 'OK' on the confirmation window.
This 'soft'-reset will not affect PROFIBUS communication on the repeater modules; the repeater functionality