Technical Data - Fiber Optic Ring Mm1 (101-201530) - Procentec ComBricks User Manual

Profibus data hub for repeaters and fiber optics modules
Table of Contents

Advertisement

25 Technical Data - Fiber Optic Ring MM1 (101-201530)

Technical Data - Fiber Optic Ring MM1 (101-201530)
Backplane
PROFIBUS networks
Modules
Power supply
Current consumption
Compatible backplane units
Protocol specifications
Supported Protocols
Address
Transmission speed
Transmission speed detection
Fiber optic cable delay
Delay time (per ring module)
Total delay between 2 modules
Fiber optic specifications
Fiber Optic wavelength
Cable type
Cable length
Optical budget
Optical Loss
Connectors
Topologies
Cascading depth
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
4 (set by dipswitches or web server)
10 (positioned in the first 10 slots)
Provided through the backplane
t.b.d.
101-200011, 101-200012, 101-200023, 101-200024,
101-200027
DP-V0, DP- V1, DP-V2, FDL, MPI, FMS, PROFIsafe, PROFIdrive
and any other FDL based protocol
NO bus address required
9.6 kbps .. 12 Mbps (including 45.45 kbps)
Auto detect (< 10 s detection and 50 s lost time)
See manual for calculation
2 TBit at 9.6 kbps .. 19.2 kbps
3 TBit at 187.5 kbps .. 45.45 kbps
4 TBit at 500kbps
10 TBit at 1.5 Mbps
20 TBit at 3 Mbps
40 TBit at 6 Mbps
80 TBit at 12 Mbps
See manual for Slot time adjustment calculation
Multimode 1310 nm
Multimode Fiber G62.5 (50) / 125 µm (OM1)
Max. 5 km (baudrate independent)
13dB
2dB per km
4 x ST/BFOC (2 channels)
Ring, point-to-point (direct, hub, split, star)
No limit, only busparameter limitation of the master