Parameterization Of The Timers And Access Periods - Technoalarm TP4-20 User Manual

4 to 20 zones control panel
Table of Contents

Advertisement

Menu
9
Time
Time
2
Timers
Timers
1
Timer 01
Timer 01
1
Action
Timer 01
2
Attribute
Timer 01
3
Programs
Programs
1
Program 01
[ # ]
Timer 01
4
Time
Time
12 : 32 [hh:mm]
Programming
3-4
3.1.5
PARAMETERIZATION OF THE TIMERS AND ACCESS
PERIODS
From the master programming menu select the submenu time.
The time menu contains 2 submenus itself:
Timers
Access periods of the codes/keys
Commands available
+ wy
to select the submenu
+ #
to confirm the selection
3.1.5.1
TIMERS
The timers permit scheduling of determined functions, such as arming/disarming of
the programs and activation/deactivation of bypass. The control panel provides 4
independent timers.
SELECTION OF THE TIMER
+ wy
to select the timer to be programmed
+ #
to confirm the selection
For every timer the following parameters can be programmed:
Action (e.g. arming/disarming, activation/deactivation of bypass)
Attribute (frequency of activation of the timer)
Programs (the timer is to act on)
Time (activation time of the timer)
Temporary block (skip the next activation)
Commands available
+ wy
to select the parameter to be programmed
+ #
to confirm the selection
ACTION
Every timer can execute one of the following actions:
Arming of the programs
Disarming of the programs
Activation of bypass
Deactivation of bypass
Activation of the remote controls
Deactivation of the remote controls
Arming with system status control
Commands available
+ wy
to select the action to be executed
+ #
to confirm the selection
+ CL-EX
to confirm programming and quit
ATTRIBUTE
Every timer can be activated with the following frequencies:
Inactive
Every day
Every working day
Every holiday eve
Commands available
+ wy
to select the attribute of activation
+ #
to confirm the selection
+ CL-EX
to confirm programming and quit
PROGRAMS
Every timer can act on the programs associated.
On the display is viewed current programming for every program:
[
]
Program not associated to the timer selected
[ # ]
Program associated to the timer selected
Commands available
+ #
to associate the program to the timer selected
+ *
to undo the existing association
+ CL-EX
to confirm and quit
TIME
Every timer can be activated at a determined hour.
Commands available
+ wy
to select the parameter to be modified
+ 0...9
to program the hour of activation
+ CL-EX
to confirm and quit
Every holiday
Every Sunday
Every Monday
Every Tuesday
Every Wednesday
Every Thursday
Every Friday
Every Saturday
User Manual - TP4-20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents