Settings - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Siemens recommends setting this time to 0 s so that it has no effect.

Settings

6.7.7.3
Addr.
General
_:1
_:2
_:119
_:8
_:118
_:120
_:10
_:26
_:27
_:3
_:6
_:113
_:114
_:116
_:115
Dyn.s: AR off/n.rdy
_:28
_:35
Dyn.set: AR cycle 1
_:29
_:36
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Parameter
C
Log.-inv.-T #:Mode
Log.-inv.-T #:Operate &
flt.rec. blocked
Log.-inv.-T #:Directional
mode
Log.-inv.-T #:Method of
measurement
Log.-inv.-T #:Directional
comparison
Log.-inv.-T #:Release via
input signal
Log.-inv.-T #:Blk. by
meas.-volt. failure
Log.-inv.-T #:Dynamic
settings
Log.-inv.-T #:Blk. w.
inrush curr. detect.
Log.-inv.-T #:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
5 A @ 100 Irated 0.15 A to 175.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Log.-inv.-T #:Time dial
Log.-inv.-T #:Min. time
of the curve
Log.-inv.-T #:Max. time
of the curve
Log.-inv.-T #:Threshold
multiplier
Log.-inv.-T #:Additional
time delay
Log.-inv.-T #:Effect. by
AR off/n.ready
Log.-inv.-T #:Stage
blocked
Log.-inv.-T #:Effected by
AR cycle 1
Log.-inv.-T #:Stage
blocked
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground
Setting Options
off
on
test
no
yes
forward
reverse
fundamental comp.
RMS value
no
yes
no
yes
no
yes
no
yes
no
yes
0.030 A to 35.000 A
0.15 A to 175.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.000 s to 60.000 s
0.000 s to 60.000 s
0.000 s to 60.000 s
1.00 to 4.00
0.000 s to 60.000 s
no
yes
no
yes
no
yes
no
yes
Default Setting
off
no
forward
fundamental
comp.
no
no
yes
no
no
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
1.250 s
1.200 s
5.800 s
1.10
0.000 s
no
no
no
no
473