Settings - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Parameter Value
disk emulation
instantaneous
Parameter: Current/time value pairs (of the dropout characteristic curve)
With these settings, you define the characteristic curve. Set a current/time value pair for each characteristic-
curve point. The setting depends on the characteristic curve you want to realize.
Set the current value as a multiple of the threshold value. Siemens recommends that you set the Threshold
parameter to 1.00 in order to obtain a simple relation. You can change the threshold value setting afterwards
if you want to shift the characteristic curve.
Set the time value in seconds. The characteristic curve is shifted via the Time dial parameter.
NOTE
i
i
The value pairs must be entered in continuous order.
Parameter: 1-pole operate allowed
Default setting (_:11) 1-pole operate allowed = no
The parameter must be set for the specific application.
Parameter Value
no
yes
Parameter: Threshold (absolute)
Default setting (_:113) Threshold (absolute) = 0.000 A
With the Threshold (absolute) parameter, you define and change the absolute pickup threshold of the
stage without changing all points of the characteristic curve.
The parameter is only used for special applications. With the default setting, this functionality is disabled. You
can find more information in
Page
349.
6.3.6.3

Settings

Addr.
General
_:1
_:2
_:11
_:26
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Description
In the case of this setting, a dropout characteristic curve has to be set in
addition to the operate curve.
Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
Select this setting if the dropout is not to be performed after disk emulation
but an instantaneous dropout is desired.
Description
The stage always operates 3-pole.
The stage operates phase-selectively. However, tripping by the device (gener-
ated in the trip logic of the Circuit-breaker function group) is always 3-pole
because the device does not support phase-selective tripping.
Pickup and Dropout Behaviors with the User-Defined Characteristic Curve ,
Parameter
C
User curve #:Mode
User curve #:Operate &
flt.rec. blocked
User curve #:1-pole
operate allowed
User curve #:Dynamic
settings
Protection and Automation Functions
6.3 Overcurrent Protection, Phases
Setting Options
off
on
test
no
yes
no
yes
no
yes
Default Setting
off
no
no
no
351