5.6 Function-Group Type Analog Units
5.6.3.3

Communication with 20-mA Unit Ethernet

Logic
[lo20mtcp-150113-01.tif, 1, en_US]
Figure 5-36
Communication with 20-mA Unit
The function is used to communicate with a 20-mA unit connected via an Ethernet connection. When a
connection of the function to an external 20-mA unit via an Ethernet interface has successfully been estab-
lished, the 20-mA unit sends the measured values of all connected channels to the function 20-mA unit.
Ether.. For the connection to be established successfully, specific communication settings must be specified.
You can find more detailed information in Chapter
The 20-mA measurement unit 7XV5674 is supported.
Error Responses
The following table lists the conditions under which the
state.
Table 5-10
Error Description
The function 20-mA unit Ether. cannot establish a
connection with a communication module.
The function 20-mA unit Ether. sends TCP settings to
the communication module, which evidently would
like to connect to the 20-mA unit via a serial protocol.
This communication module does not establish a
connection to the 20-mA unit.
The connection between the communication module
and the 20-mA unit causes a time-out indication.
240
Logic of the Function 20-mA Unit Ethernet
Error Responses
5.6.3.4 Application and Setting Notes
Health status transitions to the Alarm or Warning
Status Health
Alarm
Alarm
Warning
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
.