Siemens 7SJ82 Manual page 655

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

[lo_Stage Control, 1, en_US]
Figure 6-165
RMS-Value Selection
The protection function supports 2 kinds of RMS measurement:
Normal RMS value
Gained RMS value from the function block Filter
The gained RMS value is automatically used if the function block Filter is configured and the filter has been
enabled.
NOTE
i
i
When the function block Filter is applied, only one current measuring point I-3ph is allowed to be
connected to the 3-phase current interface of the function group.
Thermal Replica
The protection function calculates the overtemperature from the phase currents based on a thermal single-
body model according to the thermal differential equation with
[fo_diffgl-170914, 2, en_US]
With the following standardization:
[fo_normie-170914, 3, en_US]
Θ
Θ
Amb
Δ ϑ
rated obj
τ
th
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Logic Diagram of the Stage Control
Current overtemperature, in relation to the final temperature at a maximum permis-
sible phase current k I
Standardized ambient temperature, where ϑ
ature. The coupled ambient temperature ϑ
ture or the ambient temperature preset using the Default temperature param-
eter.
Overtemperature of the protected object set at rated current
Thermal time constant (temperature rise/cooling) of the protected object
6.19 Thermal Overload Protection, 3-Phase - Advanced
rated, obj
describes the coupled ambient temper-
Amb
can be the measured ambient tempera-
Amb
Protection and Automation Functions
655