Siemens 7SJ82 Manual page 539

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

[dwvebhdi-310113-01.tif, 2, en_US]
Figure 6-107
The voltage at R is, then,
V
= I
· (2R
+ R
R
1
a2
A further assumption is that the pickup value of the SIPROTEC 5 device corresponds to half of the knee-point
voltage of the current transformers. In the edge case,
V
= V
/2
R
KP
The stability limit I
stable:
[foistabl-310113-01.tif, 1, en_US]
EXAMPLE
For the 5 A transformer as above with V
Longest connection line = 22 m with 4 mm
[foisl5aw-310113-01.tif, 1, en_US]
In the example, the stability limit is 15 × rated current or 12 kA primary.
For the 1 A transformer as above with V
Longest connection line = 107 m with 2.5 mm
[foisl1aw-310113-01.tif, 1, en_US]
In the example, the stability limit is 27 × rated current or 21.6 kA primary.
Sensitivity Consideration for High-Impedance Restricted Ground-Fault Protection
The voltage present at the set of current transformers is supplied to the protection device via a series resistor R
as proportional current for evaluation. For dimensioning of the resistor, the following must be taken into
account:
The high-impedance restricted ground-fault protection should pick up at approximately half of the knee-point
voltage of the current transformers. From this, you can calculate the resistor R.
Since the device measures the current through the resistor, the resistor and measuring input of the device
must be connected in series. Since the resistor still should be high-impedance (aforementioned condition R >>
2R
+ R
), the inherent resistance of the measuring input can be neglected. The resistance results thus from
a2
i2
the pickup current I
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Simplified Connection Diagram of a Layout for High-Impedance Restricted Ground-Fault
Protection
)
i2
results, which means the through fault current up to which the arrangement remains
SL
= 75 V and R
KP
= 350 V and R
KP
and half of the knee-point voltage:
pick
= 0.3 Ω
i
2
cross-section; that corresponds to R
= 5 Ω
i
2
cross-section; that corresponds to R
Protection and Automation Functions
6.12 Overcurrent Protection, 1-Phase
= 0.1 Ω
a
= 0.75 Ω
a
539