Quality Processing/Affected By The User For Received Goose Values - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

System Functions
3.3 Processing Quality Attributes
Influencing the Quality by the User
You can influence the processing of data and their quality differently. In DIGSI 5, this is possible at the
following 3 locations:
In the Information routing editor for external signals of GOOSE connections
In the CFC chart
In the Information routing editor for binary input signals of device-internal functions
The following chapters describe in more detail the options regarding this influence as well as the automatic
quality processing.
If a GOOSE connection is the data source of a binary input signal of a device-internal function, you can influ-
ence processing of the quality at 2 locations: at the GOOSE connection and at the input signal of the function.
This is based on the following: A GOOSE date can be distributed within the receiving device to several func-
tions. The GOOSE connection setting (influence) affects all functions. However, if different functions require
customized settings, these are then set directly at the binary input signal of the function.

Quality Processing/Affected by the User for Received GOOSE Values

3.3.2
The properties of quality processing have changed with the introduction of GOOSE Later Binding. You can find
information about the former quality processing in chapter
for Received GOOSE Values, Page
In the Information Routing Editor, you can influence the data value and quality of all data types. The
following figure shows the possible influence using the example of a DPC data type. All setting options are
effective for the device receiving the data.
In the DIGSI 5 project tree, double-click Information Routing.
Select either the desired signal in the External Signals group or the signal of a function activated via the
GOOSE column.
Open the Properties window and select the Processing Quality Attributes sheet.
90
Previous Quality Processing/Affected by the User
94.
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Advertisement

Table of Contents
loading

This manual is also suitable for:

7sj85

Table of Contents