Parameter: Pickup delay
Default setting (_:103) Pickup delay = 0.00 s
With the parameter Pickup delay, you set whether pickup of the stage is to be delayed or not. If the tran-
sient cycle of the ground fault occurrence should not be evaluated, set a delay of 100 ms, for example.
Parameter: Operate delay
Default setting (_:6) Operate delay = 0.30 s
The Operate delay parameter determines the time during which the pickup conditions must be met to
issue the operate indication. The operate indication is issued when this time expires.
6.15.12.3

Settings

Addr.
Y0> #
_:1
_:2
_:10
_:27
_:101
_:102
_:103
_:6
6.15.12.4

Information List

No.
Y0> #
_:81
_:501
_:54
_:52
_:53
_:60
_:55
_:56
_:57

Pulse-Pattern Detection Stage

6.15.13
6.15.13.1

Description

Overview
The Pulse-pattern detection stage detects a faulty feeder during a permanent ground fault in overcompen-
sated systems. This method is not reliably applicable to undercompensated systems.
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Parameter
C
Y0> #:Mode
Y0> #:Operate & flt.rec.
blocked
Y0> #:Blk. by meas.-volt.
failure
Y0> #:Blk. w. inrush curr.
detect.
Y0> #:V0> threshold
value
Y0> #:Threshold Y0>
Y0> #:Pickup delay
Y0> #:Operate delay
Information
Y0> #:>Block stage
Y0> #:>Block delay & op.
Y0> #:Inactive
Y0> #:Behavior
Y0> #:Health
Y0> #:Inrush blocks operate
Y0> #:Pickup
Y0> #:Operate delay expired
Y0> #:Operate
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
Setting Options
off
on
test
no
yes
no
yes
no
yes
0.300 V to 200.000 V
0.10 mS to 100.00 mS
0.00 s to 60.00 s
0.00 s to 60.00 s
Data Class
(Type)
SPS
SPS
SPS
ENS
ENS
ACT
ACD
ACT
ACT
Default Setting
off
no
yes
no
5.000 V
2.00 mS
0.00 s
0.30 s
Type
I
I
O
O
O
O
O
O
O
619