Settings; Information List - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Function-Group Types
5.8 Process Monitor

Settings

5.8.10
Addr.
Cold-load PU
_:1
_:101
_:102
_:103
_:104
_:105

Information List

5.8.11
No.
Cold-load PU
_:81
_:500
_:501
_:54
_:52
_:53
_:300
300
Parameter
C
Cold-load PU:Mode
Cold-load PU:Operating
mode
Cold-load PU:Dropout
1 A @ 100 Irated 0.030 A to 10.000 A
threshold current
5 A @ 100 Irated 0.15 A to 50.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Cold-load PU:Dropout
delay curr.crit.
Cold-load PU:Dropout
delay CB closed
Cold-load PU:Min. CB-
open time
Information
Cold-load PU:>Block stage
Cold-load PU:>Block fast dropout
Cold-load PU:>Activate cold-load
Cold-load PU:Inactive
Cold-load PU:Behavior
Cold-load PU:Health
Cold-load PU:Cold-load pickup
Setting Options
off
on
test
I open
CB and I open
0.030 A to 10.000 A
0.15 A to 50.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
1 s to 600 s
1 s to 21600 s
0 s to 21600 s
Data Class
(Type)
SPS
SPS
SPS
SPS
ENS
ENS
SPS
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Default Setting
off
I open
1.000 A
5.00 A
1.000 A
5.00 A
1.000 A
5.000 A
600 s
3600 s
3600 s
Type
I
I
I
O
O
O
O