6.37 Power Protection (P,Q), 3-Phase

Reactive Power Stage

6.37.4
Logic of a Stage
[lo_3phase reactive power, 2, en_US]
Figure 6-232
Measured Value
The Measured value parameter is used to specify which measured power value is processed by the tripping
stage. Possible settings are positive seq. power and the phase-selective powers power of phase A,
power of phase B or power of phase C.
Pickup Characteristic
With the stage type you specify if the stage work as a greater stage (stage type: Power Q>) or as a smaller
stage (stage type: Power Q<).
The Threshold parameter is used to define the pickup threshold of the stage. The Tilt power charac-
teristic parameter is used to define the tilt of the pickup characteristic. The figure below shows the defini-
tion of the signs.
802
Logic Diagram of the Reactive Power Stage (Stage Type: Power Q<)