Function Description - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Function Description

6.22.3
Logic of the Stage
[lounbala-090812-03.tif, 1, en_US]
Figure 6-176
Method of Measurement
The stage uses the negative-sequence current I
from the measured 3-phase currents according to the defining equation of symmetrical components.
Warning Stage
If the negative-sequence current I
the
Warning indication is given after expiry of a set time Warning delay.
Thermal Characteristic Stage
The machine manufacturers indicate the permissible unbalanced load using the following formula:
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Logic Diagram of the Unbalanced-Load Protection Function
continuously exceeds the parameter Max. continuously perm. I2,
2
as a measurand. The negative-sequence current is calculated
2
Protection and Automation Functions
6.22 Unbalanced-Load Protection
687