System Functions
3.10 Device Settings
Addr.
Spontan.indic.
_:139
Test support
_:150
_:151
3.10.1.4
Information List
No.
General
_:510
_:511
_:507
_:508
_:512
_:52
_:53
_:51
_:321
_:54
_:323
_:320
Settings-Group Switching
3.10.2
3.10.2.1
Overview of Functions
For different applications you can save the respective function settings in so-called Settings groups, and if
necessary enable them quickly.
You can save up to 8 different settings groups in the device. In the process, only one settings group is active at
any given time. During operation, you can switch between settings groups. The source of the switchover can
be selected via a parameter.
You can switchover the settings groups via the following alternatives:
•
Via the on-site operation panel directly on the device
•
Via an online DIGSI connection to the device
•
Via binary inputs
•
Via a communication connection to the substation automation technology.
The communication protocols IEC 60870-5-103, IEC 60870-5-104, IEC 61850, DNP or Modbus TCP can be
used for switching the settings groups.
A settings group includes all switchable settings of the device. Except for a few exceptions (for example,
general device settings such as rated frequency), all device settings can be switched.
Detailed information about the settings groups can be found in the Operating Manual and DIGSI 5 Online
Help.
182
Parameter
C
General:Fault-display
General:Activate device
test mode
General:Oper.bin.outp.
under test
Information
General:>Test mode on
General:>Test mode off
General:>Device funct.logoff on
General:>Dev. funct.logoff off
General:>LED reset
General:Behavior
General:Health
General:Test mode
General:Protection on
General:Protection inactive
General:LED reset
General:LED have been reset
Setting Options
•
with pickup
•
with trip
•
0
•
1
•
0
•
1
Data Class
(Type)
SPS
SPS
SPS
SPS
SPS
ENS
ENS
ENC
SPC
SPS
SPC
SPS
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Default Setting
with pickup
false
false
Type
I
I
I
I
I
O
O
C
C
O
C
O