Settings; Siprotec 5, Overcurrent Protection, Manual C53000-G5040-C017-8, Edition - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
Network Structure
Ring network, meshed network Greater operational zero-sequence voltages can occur in ring or meshed
Parameter: 3I0> threshold value
Default setting (_:13021:104) 3I0> threshold value = 0.030 A
The setting is significant only for optional trip logic for switching off permanent ground faults. Select the
setting such that the static ground-fault current exceeds the threshold value. You can disable this criterion by
setting the value to 0 A.
Parameter: Dropout delay
Default setting (_:13021:7) Dropout delay = 0.00 s
The parameter Dropout delay allows you to use the function also as a protection against intermittent
ground faults. With the parameter Dropout delay, the dropout of the pickup state after fault extinction is
delayed or held until the next ignition. Thus, the operate delay can go on and trip the fault.
Set the time to a value within which the new ignition can still be assigned to the previous fault. Typical values
are in a range between several hundred milliseconds and a few seconds.
Parameter: Operate delay
Default setting (_:13021:6) Operate delay = 0.50 s
The Operate delay parameter determines the time during which the pickup conditions must be met to
issue the operate indication. The operate indication is issued when this time expires.
The setting of the Operate delay depends on the specific application. Ensure that the pickup is delayed by
100 ms regarding the time of the ground-fault ignition.
6.15.5.3

Settings

Addr.
Trans.Gnd.flt1
_:13021:1
_:13021:2
584
Description
networks.
The secondary operational zero-sequence voltages can be determined by
reading the residual voltage V
the symmetrical components from the device or via DIGSI.
In case you read the secondary residual voltage V
with the Matching ratio Vph / VN parameter. You can find more
information in chapter
Point Voltage 3-Phase
If V
is greater than 2.5 V, the value of Maximum operational V0
0 sec
shall be increased to V
Example:
V
= 5.000 V
N sec
Matching ratio Vph / VN = √3
V
= 5.000 V ⋅ √3 / 3 = 2.887 V
0 sec
Maximum operational V0 = 2.887 V ⋅ 1.2 = 3.464V
In most cases, the operational zero-sequence voltages are smaller than
2.500 V. Siemens recommends using the default value of 3.000 V.
Parameter
C
Trans.Gnd.flt1:Mode
Trans.Gnd.flt1:Operate &
flt.rec. blocked
or the zero-sequence voltage V
N sec
N sec
6.1.6 Application and Setting Notes for Measuring
(V-3ph).
⋅ 1.2.
0 sec
Setting Options
off
on
test
no
yes
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
under
0 sec
, you convert it to V
0 sec
Default Setting
off
no