Settings - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Parameter: Trip interface contains
Default setting (_:13921:101) Trip interface contains = operate (grid)
The stage provides 2 operate signals, the
You use the Trip interface contains parameter to define whether one or none of them will be
forwarded to the trip interface of the circuit-breaker interaction. The selected operate signal will trip the circuit
breaker that has been connected to the protection function group.
The setting depends on the specific application.
Parameter: Q sign
Default setting (_:13921:102) Q sign = not reversed
The default directions of the positive reactive-power flow Q and the forward direction of the short-circuit
protection are identical, in the direction of the main protected object (for example, a feeder). You use the Q
sign parameter to reverse the sign and therefore the direction of the reactive-power flow Q. This reversal
may be required for specific application, where the main protected object (for example, a line towards the
main power systems) is in different direction to the power-generation facility.
Parameter Value
not reversed
reversed
6.40.3.3

Settings

Addr.
Prot. stage 1
_:13921:1
_:13921:2
_:13921:10
_:13921:27
_:13921:101
_:13921:102
_:13921:3
_:13921:103
_:13921:105
_:13921:108
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Operate (generator) and the Operate (grid) .
Parameter
C
Prot. stage 1:Mode
Prot. stage 1:Operate &
flt.rec. blocked
Prot. stage 1:Blk. by
meas.-volt. failure
Prot. stage 1:Blk. w.
inrush curr. detect.
Prot. stage 1:Trip inter-
face contains
Prot. stage 1:Q sign
Prot. stage 1:Q>
threshold value
Prot. stage 1:V<
threshold value
Prot. stage 1:I> release
1 A @ 100 Irated 0.030 A to 10.000 A
threshold
5 A @ 100 Irated 0.15 A to 50.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Prot. stage 1:Oper. delay
generator CB
6.40 Undervoltage-Controlled Reactive-Power Protection
Description
The protected object is in the same direction as the power-gener-
ation facility.
The protected object is not in the same direction as the power-
generation facility.
Setting Options
off
on
test
no
yes
no
yes
no
yes
no operate
operate (generator)
operate (grid)
not reversed
reversed
1.00 % to 200.00 %
3.000 V to 175.000 V
0.030 A to 10.000 A
0.15 A to 50.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.00 s to 60.00 s
Protection and Automation Functions
Default Setting
off
no
yes
no
operate (grid)
not reversed
5.00 %
85.000 V
0.100 A
0.50 A
0.100 A
0.50 A
0.100 A
0.500 A
0.50 s
831