Protection and Automation Functions
6.33 Underfrequency Protection
Both methods of measurement are characterized by a high measuring accuracy combined with a short
response time. Disturbance values such as harmonics, high frequency disturbances, phase-angle jumps during
switching operations and compensation processes due to power swings are effectively suppressed.
Behavior on Leaving the Operating Range
The sampling-frequency tracking makes a wide frequency operating range possible. If the stage has picked up
before leaving the frequency operating range and the measuring voltage is higher than the set minimum
voltage, the pickup is maintained. A dropout of the pickup is only possible by means of a blocking.
Blocking the Stage
In the event of blocking, a picked-up stage will be reset. The following blocking options are available for the
stage:
Via the binary input signal
Internally when the voltage drops below the Minimum voltage
6.33.4

Application and Setting Notes

Frequency-Measurement Method
The frequency measurement method is selected with the functional configuration from the DIGSI functions
library. The letter at the end of the function name describes the method of measurement.
Redundant solutions can be implemented by combining 2 different methods of frequency measurement. You
can implement a 2-out-of-2 decision by connecting the operate indications of both functions in a CFC with a
logical AND gate. This increases the reliability of protection.
Method of Measurement
Angle difference method
(method A)
Filtering method (method B)
Parameter: Threshold
Recommended setting value (_:61:3) Threshold = 49.80 Hz for f
The Threshold parameter is used to define the pickup threshold of the underfrequency protection stage in
dependence of the application. 49.8 Hz is a typical warning threshold in 50-Hz systems.
Parameter: Operate delay
Recommended setting value (_:61:6) Operate delay = 10.00 s
The Operate delay parameter is used to set the stage so that overfunctions due to disturbing influences
(for example, switching operations) are avoided. Fairly high time delays are sufficient for warning indications.
Parameter: Minimum voltage
Recommended setting value (_:2311:101) Minimum voltage = 37 500 V
For the Undervoltage blocking, 65 % of the protected object's rated voltage is recommended.
When determining the setting value, please keep in mind the measurement method and the measuring
connection that you have selected. If you work with the positive-sequence voltage, remember that the
maximum voltage is equal to the phase-to-ground voltage. The default setting is referred to this value.
Parameter: Dropout differential
Recommended setting value (_:2311:109) Dropout differential = 20 mHz
770
>Block stage from an external or internal source
Description
Select this method of measurement if the frequency protection stage is
used for the protection of machines.
Select this method of measurement if the frequency protection stage is
used in an electrical power system.
= 50 Hz
rated
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017