The Threshold parameter is used to define the pickup threshold of the stage. The Tilt power charac-
teristic parameter is used to define the tilt of the pickup characteristic. The figure below shows the defini-
tion of the signs.
[dw_tilt-power active power, 2, en_US]
Figure 6-231
Pickup
The stage compares the selected power value with the set Threshold. Depending on the stage type (Power
P> or Power P<) being above or falling below the threshold value will lead to a pickup.
Dropout Delay
A delay can be set for the dropout when the measured value falls below the dropout threshold. The pickup is
maintained for the specified time. The time delay of the tripping (parameter Operate delay) continues to
run. Once the Operate delay has elapsed, the stage trips.
Blocking the Stage
In the event of blocking, the picked up stage will be reset. Blocking the stage is possible externally or internally
via the binary input signal
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Tilt-Power Characteristic
>Block stage .