Settings - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Parameter Value
on
off
NOTE
i
i
Because of the flexible setting options of the voltage measurand, the function itself does not determine the
current associated with the voltage. A suitable current-flow monitoring function must be created by the
user with the Continuous Function Chart (CFC), and connected to the binary input signal >Current
flow-criterion.
Operation as Supervision Function
If you want the tripping stage to have a reporting effect only, generation of the operate indication and fault
logging can be disabled via the Operate & flt.rec. blocked parameter.

Settings

6.31.5
Addr.
General
_:2311:101
Stage 1
_:571:1
_:571:2
_:571:9
_:571:8
_:571:3
_:571:4
_:571:6
Stage 2
_:572:1
_:572:2
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Description
Because of the application, it makes sense that the stage is only active (that
is, not blocked) when a certain current flow is present (see note).
Current flow monitoring does not make sense for the application.
Parameter
C
General:Current-flow
criterion
Stage 1:Mode
Stage 1:Operate &
flt.rec. blocked
Stage 1:Measured value
Stage 1:Method of
measurement
Stage 1:Threshold
Stage 1:Dropout ratio
Stage 1:Operate delay
Stage 2:Mode
Stage 2:Operate &
flt.rec. blocked
Protection and Automation Functions
6.31 Undervoltage Protection with Any Voltage
Setting Options
off
on
off
on
test
no
yes
VA measured
VB measured
VC measured
VAB measured
VBC measured
VCA measured
VAB calculated
VBC calculated
VCA calculated
V0 calculated
fundamental comp.
RMS value
0.300 V to 340.000 V
1.01 to 1.20
0.00 s to 60.00 s
off
on
test
no
yes
Default Setting
on
off
no
VA measured
fundamental
comp.
80.000 V
1.05
3.00 s
off
no
761