Addr.
_:2
_:113
_:8
_:112
_:114
_:10
_:26
_:27
_:3
_:110
_:101
Dyn.s: AR off/n.rdy
_:28
_:35
Dyn.set: AR cycle 1
_:29
_:36
_:14
_:102
Dyn.set: AR cycle 2
_:30
_:37
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Parameter
C
User curve #:Operate &
flt.rec. blocked
User curve #:Directional
mode
User curve #:Method of
measurement
User curve #:Directional
comparison
User curve #:Release via
input signal
User curve #:Blk. by
meas.-volt. failure
User curve #:Dynamic
settings
User curve #:Blk. w.
inrush curr. detect.
User curve #:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
5 A @ 100 Irated 0.15 A to 175.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
User curve #:Reset
User curve #:Time dial
User curve #:Effect. by
AR off/n.ready
User curve #:Stage
blocked
User curve #:Effected by
AR cycle 1
User curve #:Stage
blocked
User curve #:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
5 A @ 100 Irated 0.15 A to 175.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
User curve #:Time dial
User curve #:Effected by
AR cycle 2
User curve #:Stage
blocked
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground
Setting Options
•
no
•
yes
•
forward
•
reverse
•
fundamental comp.
•
RMS value
•
no
•
yes
•
no
•
yes
•
no
•
yes
•
no
•
yes
•
no
•
yes
0.030 A to 35.000 A
0.15 A to 175.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
•
instantaneous
•
disk emulation
0.05 to 15.00
•
no
•
yes
•
no
•
yes
•
no
•
yes
•
no
•
yes
0.030 A to 35.000 A
0.15 A to 175.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.05 to 15.00
•
no
•
yes
•
no
•
yes
Default Setting
no
forward
fundamental
comp.
no
no
yes
no
no
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
disk emulation
1.00
no
no
no
no
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
1.00
no
no
483