System Functions
3.9 General Notes for Setting the Threshold Value of Protection Functions
[scumzpri_5, 1, en_US]
Figure 3-96
When switching over to the percent view, the result should be the following value:
1500 A/1000 A · 100 % = 150 %
174
Example of the Threshold Value of the Definite Time-Overcurrent Protection (Edit Mode:
Primary)
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017