Stage Description

6.24.3
Logic of a Stage
[loovpu03-090611-01.tif, 2, en_US]
Figure 6-184
Measured Value, Method of Measurement
The device measures the residual voltage at the broken-delta winding. The measured voltage is converted to
the zero-sequence voltage V
sequence voltage V
defining equation.
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Logic Diagram of an Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage
Stage
. If the residual voltage is not available to the device as a measurand, the zero-
0
is calculated from the measured phase-to-ground voltages V
0
6.24 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage
Protection and Automation Functions
, V
, and V
using the
A
B
C
705