Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Quality Attribute: Test
The input signal source is in a test state
and the function to be processed is in
normal state.
Quality Attribute OperatorBlocked
The quality cannot be influenced at this position and does not lead to a response within the logic
Output Data
The quality is not processed through the actual algorithm/logic of the function. The following table displays
the conditions required to set the quality of output signals of a function.
Cause
Functional state = Test
(thus, result of device operating
mode = Test or function mode
= Test)
Functional state = Off
(thus, result of device operating
mode = Off)
Function health = Alarm
(for example, result of invalid
receive data)
Device operating mode = func-
tionally logged off
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
The data value of the source signal is ignored. You can select
between the following options:
Further processing of the last valid source signal data value,
before the source switches to the test state (that is the
default setting)
The binary value to be processed further is set to 0.
The binary value to be processed further is set to 1.
This configuration option is necessary to satisfy different applica-
tions.
D0 Value
Unchanged
Function-specific, corre-
sponding to the definition for
switched off
Function-specific, corre-
sponding to the definition for
reset
Unchanged
3.3 Processing Quality Attributes
Quality Attribute
After internal (to
To the IEC 61850
the SIPROTEC 5
interface, in buffer
system, for example,
in the direction of a
CFC chart)
Test =
Test =
TRUE
Validity =
Validity =
good
Validity =
Validity =
good
Validity =
Validity =
good
OperatorBlocked =
detailQual =
TRUE
oldData
OperatorBlocked =
TRUE
System Functions
TRUE
invalid
invalid
good
103