Information List; Blocking Of The Tripping By Device-Internal Inrush-Current Detection; Description - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Protection and Automation Functions
6.3 Overcurrent Protection, Phases
Addr.
_:19
_:107

Information List

6.3.6.4
No.
User curve #
_:81
_:84
_:500
_:54
_:52
_:53
_:60
_:62
_:63
_:64
_:65
_:66
_:67
_:68
_:59
_:55
_:56
_:57

Blocking of the Tripping by Device-Internal Inrush-Current Detection

6.3.7
6.3.7.1

Description

With the Blk. w. inrush curr. detect. parameter, you can define whether tripping of the stage
should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking, the
stage picks up. The start of the tripping delay and the trip signal are blocked. The function signals this through
a corresponding indication. If the blocking drops out and the threshold value of the stage is still exceeded, the
time delay is started. After that time, the stage operates. The following figure only shows the part of the stage
(exemplified by definite-time overcurrent protection stage 1) that illustrates the influence of the blocking.
Only if the central function Inrush-current detection (see chapter
can the blocking be set.
354
Parameter
C
User curve #:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
5 A @ 100 Irated 0.15 A to 175.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
User curve #:Time dial
Information
User curve #:>Block stage
User curve #:>Activ. dyn. settings
User curve #:>Block delay & op.
User curve #:Inactive
User curve #:Behavior
User curve #:Health
User curve #:Inrush blocks operate
User curve #:Dyn.set. AR cycle1act.
User curve #:Dyn.set. AR cycle2act.
User curve #:Dyn.set. AR cycle3act.
User curve #:Dyn.set. ARcycl.>3act
User curve #:Dyn.set. CLP active
User curve #:Dyn.set. BI active
User curve #:Dyn. set. blks. pickup
User curve #:Disk emulation running
User curve #:Pickup
User curve #:Operate delay expired
User curve #:Operate
Setting Options
0.030 A to 35.000 A
0.15 A to 175.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.05 to 15.00
Data Class
(Type)
SPS
SPS
SPS
SPS
ENS
ENS
ACT
SPS
SPS
SPS
SPS
SPS
SPS
SPS
SPS
ACD
ACT
ACT
12.10 Inrush-Current
Detection) is in effect
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Default Setting
1.500 A
7.50 A
1.500 A
7.50 A
1.500 A
7.500 A
1.00
Type
I
I
I
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O

Advertisement

Table of Contents
loading

This manual is also suitable for:

7sj85

Table of Contents