Settings; Information List - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Parameter: Minimum voltage V1
Default setting (_:2311:102) Minimum voltage V1 = 5.000 V
With the parameter Minimum voltage V1, you can limit the operating range of the reverse-power protec-
tion. If the positive-sequence voltage falls below the set value, the reverse-power protection is deactivated. If
no other restrictions are known, Siemens recommends using the default setting.
6.38.3.3

Settings

Addr.
General
_:2311:101
_:2311:102
6.38.3.4

Information List

No.
General
_:2311:300
_:2311:301
_:2311:302
_:2311:303
_:2311:304
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Parameter
C
General:Angle correction
General:Minimum
voltage V1
Information
General:Undervoltage blocking
General:P1avg
General:Q1avg
General:P1fast
General:Q1fast
Protection and Automation Functions
6.38 Reverse-Power Protection
Setting Options
-10.00 ° to 10.00 °
0.300 V to 60.000 V
Data Class
(Type)
SPS
MV
MV
MV
MV
Default Setting
0.00 °
5.000 V
Type
O
O
O
O
O
813