Figure 6-93
For this example, the following is assumed:
The current-flow criterion offers additional security to prevent unwanted tripping caused by sudden light
influences.
Depending on the arc location in the cable-connection compartment of the feeder, it is not always
possible to measure the current. If an arc is detected in the cable-connection compartment of the feeder,
the current will therefore be evaluated in the infeed.
Install the optical point sensors in the busbar compartment, the circuit-breaker compartment, and the
cable-connection compartment of the feeders as well as the busbar compartment of the infeed. Connect
the optical point sensors to the protection device in the infeed.
The protection device in the infeed clears all arcs in the busbar compartment, the circuit-breaker
compartment, and the cable-connection compartment of feeder 1 and 2. Furthermore, the protection
device clears arcs in the busbar compartment of the infeed.
If the optical point sensors in the busbar compartment, the circuit-breaker compartment, and the cable-
connection compartment of the feeders, or in the busbar compartment of the infeed detect an arc, the
protection device in the infeed evaluates the current as well.
If an arc occurs in the circuit-breaker compartment and in the cable-connection compartment of the
infeed, the superordinate protection device must trip.
NOTE
i
i
If the Arc protection function operates with the Operating mode = current and light, the addi-
tional current-flow criterion prevents unwanted tripping caused by external light influences.
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Layout and Connection of the Optical Point Sensors (Operating Mode = Current and Light)
Protection and Automation Functions
6.10 Arc Protection