System Functions
3.8 Other Functions
[scparafl-291110-01.tif, 2, en_US]
Figure 3-80
The chatter-blocking settings have the following meaning (see also
ples shown in the following):
No. permis.state changes
This number specifies how often the state of a signal may toggle within the chatter-test time and the
chatter-checking time. If this number is exceeded, the signal will be or remains blocked.
Enter a number from 0 to 65535 in this field. If the entry is 0, chatter blocking is essentially inactive.
Initial test time
During this time, the number of times a signal changes its status is checked. This time is started if chatter
blocking is configured for at least one signal and this signal changes its status. If the configured number
of permissible status changes is exceeded during the initial test time, the signal is temporarily blocked
and the indication
Enter a number between 1 and 65535 in this field. The number entered corresponds to the time in
seconds. When the set time has expired, the timer restarts automatically (cycle time).
No. of chatter tests
This number specifies the maximum number of test cycles to be run. If the number of permissible status
changes of the signal stays exceeded during the initial test time of the last test cycle, the signal is finally
blocked. In this case, the indication
additionally to the
removes this block again.
Enter a number from 0 to 32767 in this field. The value Infinite (∞) is also permissible here.
Enter this value as character string oo.
Chatter idle time
If the number of permissible status changes for a signal is exceeded during the initial test time or the
subsequent test time, the Chatter idle time starts. Within this time, this signal is blocked tempora-
rily and the
quality.
Enter a number between 1 and 65535 in this field. The number entered corresponds to the time in
minutes. An entry here is only considered if the number of chatter tests does not equal 0.
162
Chatter-Blocking Settings
Chatter blocking is set.
Group warning (Alarm handling group and Device group) is set
Chatter blocking indication after expiry of the set number. Restarting the devices
Chatter blocking indication is set. The blocked input signal is assigned the oscillatory
Figure 3-81
and
Figure 3-82
SIPROTEC 5, Overcurrent Protection, Manual