[dw_TOLP_Predefined curve, 1, en_US]
Figure 6-171

Settings

6.20.5
Addr.
General
_:1
_:2
_:102
_:104
_:105
_:106
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Example of the User-Defined Characteristic Curve
Parameter
User charact.#:Mode
User charact.#:Operate
& flt.rec. blocked
User charact.#:Threshold
current warning
User charact.#:Threshold
thermal warn.
User charact.#:Dropout
threshold operate
User charact.#:Emerg.
start T overtravel
6.20 Thermal Overload Protection, User-Defined Characteristic Curve
C
Setting Options
off
on
test
no
yes
1 A @ 100 Irated 0.030 A to 35.000 A
5 A @ 100 Irated 0.15 A to 175.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
5 A @ 50 Irated
0.15 A to 175.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
50 % to 100 %
50 % to 99 %
0 s to 15000 s
Protection and Automation Functions
Default Setting
off
no
1.000 A
5.00 A
1.000 A
5.00 A
1.000 A
5.000 A
90 %
90 %
300 s