What this chapter contains

The chapter contains preventive maintenance instructions and LED indicator
descriptions.
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
The table lists the routine maintenance intervals recommended by ABB.
Maintenance
Reforming of capacitors
Check of dustiness, corrosion
and temperature
Replacement of the cooling fan
(frame sizes R1...R4)
Check and tightening of the
power terminals
Replacement of the battery in
the assistant control panel
Testing of Safe torque off (STO)
operation and reaction
Consult your local ABB Service representative for more details on the maintenance.
On the Internet, go to
Maintenance and Field Services.
Maintenance and hardware diagnostics 369
Interval
Every year when
stored
Every year
Every three years
Every six years
Every ten years
Every year
http://www.abb.com/drives
16
Instruction
See
Capacitors
on page 371.
See
Cooling fan
on page 370.
See
Power connections
See
Changing the battery in the
assistant control panel
See
Appendix: Safe torque off (STO)
on page 417.
and select Drive Services –
on page 371.