All parameters
No.
Name/Value
DI3(INV)
DI4(INV)
DI5(INV)
1605 USER PAR
SET CHG
NOT SEL
DI1
DI2
DI3
DI4
DI5
DI1,2
DI2,3
DI3,4
DI4,5
Description
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
Enables the change of the User parameter set through a
digital input. See parameter
change is only allowed when the drive is stopped. During
the change, the drive will not start.
Note: Always save the User parameter set with parameter
9902
after changing any parameter setting, or reperforming
the motor identification. The last settings saved by the user
are loaded into use whenever the power is switched off and
on again or the parameter
unsaved changes will be lost.
Note: The value of this parameter is not included in the
User parameter sets. A setting once made remains despite
User parameter set change.
Note: Selection of User parameter set 2 can be supervised
through relay outputs RO 1...4 and digital output DO. See
parameters
1401 RELAY OUTPUT 1
OUTPUT
3,
1410 RELAY OUTPUT 4
SIGNAL.
User parameter set change is not possible through a digital
input. Parameter sets can be changed only from the control
panel.
User parameter set control through digital input DI1. Falling
edge of digital input DI1: User parameter set 1 is loaded into
use. Rising edge of digital input DI1: User parameter set 2 is
loaded into use.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
User parameter set selection through digital inputs DI1 and
DI2. 1 = DI active, 0 = DI inactive.
DI1
DI2 User parameter set
0
0
User parameter set 1
1
0
User parameter set 2
0
1
User parameter set 3
See selection DI1,2.
See selection DI1,2.
See selection DI1,2.
Actual signals and parameters 211
9902 APPLIC
MACRO. The
9902
setting is changed. Any
...
1403 RELAY
and
1805 DO
Def/FbEq
-3
-4
-5
NOT SEL
0
1
2
3
4
5
7
8
9
10