CODE FAULT
1004
PAR AO SCALE
(6320)
0307
bit 15
1005
PAR PCU 2
(6320)
0307
bit 15
1006
PAR EXT RO
(6320)
0307
bit 15
(programmable
fault function
3027)
1007
PAR FBUSMISS
(6320)
0307
bit 15
1009
PAR PCU 1
(6320)
0307
bit 15
1015
PAR USER U/F
(6320)
0307
bit 15
CAUSE
Incorrect analog output
AO signal scaling
Incorrect motor nominal
power setting
Incorrect relay output
extension parameters
Fieldbus control has not
been activated.
Incorrect motor nominal
speed/frequency setting
Incorrect voltage to
frequency (U/f) ratio
voltage setting.
Fault tracing 365
WHAT TO DO
Check parameter group
OUTPUTS
settings. Check that
following applies:
1504 MINIMUM AO1
1505 MAXIMUM
AO1.
Check parameter
9909 MOTOR NOM
POWER
setting. Following must
apply:
• 1.1 <
(9906 MOTOR NOM CURR
9905 MOTOR NOM VOLT
P
) < 3.0
N
Where P
= 1000 ·
9909 MOTOR
N
NOM POWER
(if units are in kW)
or P
= 746 ·
9909 MOTOR NOM
N
POWER
(if units are in hp).
Check parameter settings. Check that
following applies:
• Output relay module MREL-01 is
connected to drive. See parameter
0181
EXTENSION.
1402 RELAY OUTPUT
RELAY OUTPUT 3
RELAY OUTPUT 4
values.
See MREL-01 output relay module
user's manual (3AUA0000035974
[English]).
Check fieldbus parameter settings.
See chapter
Fieldbus control with
fieldbus adapter
on page 339.
Check parameter settings. Following
must apply for induction motor:
• 1 < (60 ·
9907 MOTOR NOM FREQ
/
9908 MOTOR NOM
• 0.8 <
9908 MOTOR NOM SPEED
(60 ·
9907 MOTOR NOM FREQ
9913 MOTOR POLE
0.992
Following must apply for permanent
magnet synchronous motor:
9908 MOTOR NOM SPEED
(60 ·
9907 MOTOR NOM FREQ
9913 MOTOR POLE
Check parameter
2610 USER
DEFINED U1
...
2617 USER
DEFINED F4
settings.
15 ANALOG
<
·
· 1.73 /
2,
1403
and
1410
have non-zero
SPEED) < 16
/
/
PAIRS) <
/
/
PAIRS) = 1.0