Example - ABB ACS355 series User Manual

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

A parameter which is triggered by a timed function can be connected to only one
timed function at a time.
Timed function 1
3626 TIMED FUNC 1 SRC
Timed function 2
3627 TIMED FUNC 2 SRC

Example

Air conditioning is active on weekdays from 8:00 to 15:30 (8 a.m to 3:30 p.m) and on
Sundays from 12:00 to 15:00 (12 to 3 p.m). By pressing the extension time switch,
the air-conditioning is on for an extra hour.
Parameter
3601 TIMERS ENABLE
3602 START TIME 1
3603 STOP TIME 1
3604 START DAY 1
3605 STOP DAY 1
3606 START TIME 2
3607 STOP TIME 2
3608 START DAY 2
3609 STOP DAY 2
3622 BOOSTER SEL
3623 BOOSTER TIME
3626 TIMED FUNC 1 SRC
1001 EXT1 COMMANDS
1002 EXT2 COMMANDS
1102 EXT1/EXT2 SEL
1201 CONST SPEED SEL
1209 TIMED MODE SEL
1401 RELAY OUTPUT 1
1402 RELAY OUTPUT
1410 RELAY OUTPUT 4
1805 DO SIGNAL
4027 PID 1 PARAM SET
4228 ACTIVATE
8402 SEQ PROG START
8406 SEQ LOGIC VAL 1
8425/35/45/55/65/75/85/95
8426/36/46/56/66/76/86/96
Setting
DI1
08:00:00
15:30:00
MONDAY
FRIDAY
12:00:00
15:00:00
SUNDAY
SUNDAY
DI5
(cannot be the same as parameter
01:00:00
T1+T2+B
Program features 167