All parameters
No.
Name/Value
2205 ACCELER
TIME 2
0.0...1800.0 s
2206 DECELER
TIME 2
0.0...1800.0 s
2207 RAMP SHAPE
2
0.0 = LINEAR
0.1...1000.0 s
2208 EMERG DEC
TIME
0.0...1800.0 s
2209 RAMP INPUT 0 Defines the control for forcing the speed to 0 with the
NOT SEL
DI1
DI2
DI3
DI4
DI5
Description
Defines the acceleration time 2, ie, the time required for the
speed to change from zero to the speed defined by
parameter
2008 MAXIMUM FREQ
MAXIMUM SPEED
(in vector control). The control mode is
selected by parameter
See parameter
2202 ACCELER TIME
Acceleration time 2 is used also as jogging acceleration
time. See parameter
Time
Defines the deceleration time 2, ie, the time required for the
speed to change from the value defined by parameter
MAXIMUM FREQ
(in scalar control) /
SPEED
(in vector control) to zero. The control mode is
selected by parameter
See parameter
2203 DECELER TIME
Deceleration time 2 is used also as jogging deceleration
time. See parameter
Time
Selects the shape of the acceleration/deceleration ramp 2.
The function is deactivated during emergency stop.
During jogging, parameter value is set to zero (ie, linear
ramp). See
1010 JOGGING
See parameter
2204 RAMP SHAPE
Defines the time within which the drive is stopped if an
emergency stop is activated. See parameter
STOP
SEL.
Time
currently used deceleration ramp (see parameters
DECELER TIME 1
and
Not selected
Digital input DI1. Defines digital input
forcing the speed to zero.
• Activating the digital input forces the speed to zero, after
which the speed will stay at zero.
• De-activating the digital input: speed control resumes
normal operation.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Actual signals and parameters 235
(in scalar control) /
9904 MOTOR CTRL
1.
1010 JOGGING
SEL.
2002 MAXIMUM
9904 MOTOR CTRL
1.
1010 JOGGING
SEL.
SEL.
1.
2206 DECELER TIME
1 as the control for
DI
Def/FbEq
60.0 s
2002
MODE.
1 = 0.1 s
60.0 s
2008
MODE.
1 = 0.1 s
0.0 =
LINEAR
1 = 0.1 s
1.0 s
2109 EMERG
1 = 0.1 s
NOT SEL
2203
2).
0
1
2
3
4
5

Hide quick links: