ABB ACS355 series User Manual page 359

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

CODE FAULT
0007
AI1 LOSS
(8110)
0305
bit 6
(programmable
fault function
3001, 3021)
0008
AI2 LOSS
(8110)
0305
bit 7
(programmable
fault function
3001, 3022)
CAUSE
Missing input power line
phase.
Blown fuse
Rectifier bridge internal
fault.
Analog input AI1 signal
has fallen below limit
defined by parameter
3021 AI1 FAULT
LIMIT.
Analog input signal is
weak or does not exist.
Analog input signal is
lower than fault limit.
Analog input AI2 signal
has fallen below limit
defined by parameter
3022 AI2 FAULT
LIMIT.
Analog input signal is
weak or does not exist.
Analog input signal is
lower than fault limit.
Fault tracing 359
WHAT TO DO
Measure the input and DC voltage
during start, stop and running by using
a multimeter or check parameter
DC BUS
VOLTAGE.
Check the condition of input fuses.
Replace the drive.
Check the source and wire
connections of the analog input.
Check parameters
3001 AI<MIN
FUNCTION
and
3021 AI1 FAULT
LIMIT.
.
Check the source and wire
connections of analog input.
Check parameters
3001 AI<MIN
FUNCTION
and
3021 AI1 FAULT
LIMIT.
0107