ABB drives profile (EFB) Status word, parameter
Bit
Name
8
AT_SETPOINT
9
REMOTE
10
ABOVE_LIMIT
11
EXT CTRL LOC
12
EXT RUN
ENABLE
13
Reserved
...
15
Fieldbus control with embedded fieldbus 331
Value
STATE/Description
(Correspond to states/boxes in the state diagram)
1
OPERATING. Actual value equals reference value (= is
within tolerance limits, ie, in speed control the difference
between the output speed and the speed reference is less
than or equal to 4/1%* of the nominal motor speed).
* Asymmetric hysteresis: 4% when speed exits the
reference area, 1% when speed enters the reference area.
0
Actual value differs from reference value (= is outside
tolerance limits).
1
Drive control location: REMOTE (EXT1 or EXT2)
0
Drive control location: LOCAL
1
Supervised parameter value exceeds the supervision high
limit. Bit value is 1 until the supervised parameter value falls
below the supervision low limit. See parameter group
SUPERVISION, parameter
0
Supervised parameter value falls below the supervision low
limit. Bit value is 0 until the supervised parameter value
exceeds the supervision high limit. See parameter group
SUPERVISION, parameter
1
External control location EXT2 selected
0
External control location EXT1 selected
1
External Run enable signal received
0
No external Run enable received
5320 EFB PAR 20
3201 SUPERV 1
3201 SUPERV 1
32
PARAM.
32
PARAM.