Parameters

All parameters
No.
Name/Value
10 START/STOP/DIR The sources for external start, stop and direction control
1001 EXT1
COMMANDS
NOT SEL
DI1
DI1,2
DI1P,2P
DI1P,2P,3
DI1P,2P,3P
Description
Defines the connections and the source for the start, stop
and direction commands for external control location 1
(EXT1).
Note: Start signal must be reset if the drive has been
stopped through STO (Safe torque off) input (see parameter
3025 STO
OPERATION) or emergency stop selection (see
parameter
2109 EMERG STOP
No start, stop and direction command source
Start and stop through digital input DI1. 0 = stop, 1 = start.
Direction is fixed according to parameter
(setting
REQUEST
= FORWARD).
Start and stop through digital input DI1. 0 = stop, 1 = start.
Direction through digital input DI2. 0 = forward, 1 = reverse.
To control direction, parameter
must be REQUEST.
Pulse start through digital input DI1. 0 -> 1: Start. (In order to
start the drive, digital input DI2 must be activated prior to the
pulse fed to DI1.)
Pulse stop through digital input DI2. 1 -> 0: Stop. Direction
of rotation is fixed according to parameter
(setting
REQUEST
= FORWARD).
Note: When the stop input (DI2) is deactivated (no input),
the control panel start and stop keys are disabled.
Pulse start through digital input DI1. 0 -> 1: Start. (In order to
start the drive, digital input DI2 must be activated prior to the
pulse fed to DI1.)
Pulse stop through digital input DI2. 1 -> 0: Stop. Direction
through digital input DI3. 0 = forward, 1 = reverse. To control
direction, parameter
REQUEST.
Note: When the stop input (DI2) is deactivated (no input),
the control panel start and stop keys are disabled.
Pulse start forward through digital input DI1. 0 -> 1: Start
forward. Pulse start reverse through digital input DI2. 0 -> 1:
Start reverse. (In order to start the drive, digital input DI3
must be activated prior to the pulse fed to DI1/DI2). Pulse
stop through digital input DI3. 1 -> 0: Stop. To control the
direction, parameter
REQUEST.
Note: When the stop input (DI3) is deactivated (no input),
the control panel start and stop keys are disabled.
Actual signals and parameters 191
SEL).
1003 DIRECTION
1003 DIRECTION
1003 DIRECTION
1003 DIRECTION
setting must be
1003 DIRECTION
setting must be
Def/FbEq
DI1,2
0
1
2
setting
3
4
5