ABB ACS355 series User Manual page 366

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

366 Fault tracing
CODE FAULT
1017
PAR SETUP 1
(6320)
0307
bit 15
CAUSE
Only two of the following
can be used
simultaneously: MTAC-
01 pulse encoder
interface module,
frequency input signal or
frequency output signal.
WHAT TO DO
Disable frequency output, frequency
input or encoder:
• change transistor output to digital
mode (value of parameter
MODE
= 0 [DIGITAL]), or
• change frequency input selection to
other value in parameter groups
11 REFERENCE SELECT,
40 PROCESS PID SET 1,
41 PROCESS PID SET 2
42 EXT / TRIM
PID, or
• disable (parameter
ENCODER
ENABLE) and remove
MTAC-01 pulse encoder interface
module.
1804 TO
and
5002

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents