Freq In & Tran Out - ABB ACS355 series User Manual

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

All parameters
No.
Name/Value
1611 PARAMETER
VIEW
DEFAULT
FLASHDROP
1612 FAN
CONTROL
AUTO
ON
1613 FAULT RESET Resets the current fault.
DEFAULT
RESET NOW
18 FREQ IN & TRAN
OUT
1801 FREQ INPUT
MIN
0...16000 Hz
1802 FREQ INPUT
MAX
0...16000 Hz
Description
Selects the parameter view, ie, which parameters are
shown.
Note: This parameter is visible only when it is activated by
the optional FlashDrop device. FlashDrop is designed for
fast copying of parameters to unpowered drives. It allows for
easy customization of the parameter list, eg, selected
parameters can be hidden. For more information, see
MFDT-01 FlashDrop user's manual (3AFE68591074
[English]).
FlashDrop parameter values are activated by setting
parameter
9902 APPLIC MACRO
Complete long and short parameter lists
FlashDrop parameter list. Does not include short parameter
list. Parameters which are hidden by the FlashDrop device
are not visible.
Selects the fan to be switched on and off automatically or
keeps the fan on all the time.
When the drive is used in ambient temperatures of 35 °C
(95 °F) and above, it is recommended to have the cooling
fan always on (selection ON).
Automatic fan control. The fan is switched on when the drive
is modulating. After the drive has stopped, the fan stays on
until the temperature of the drive has dropped below 55 °C
(131 °F). The fan then remains switched off until either the
drive is started or the temperature increases above 65 °C
(149 °F).
If the control board is powered from an external 24 V power
supply, the fan is switched off.
Fan always on
No reset done. Current status continues.
Resets the current fault. After reset, the parameter value
returns to DEFAULT.
Frequency input and transistor output signal processing.
Defines the minimum input value when DI5 is used as a
frequency input. See section
Minimum frequency
Defines the maximum input value when DI5 is used as a
frequency input. See section
Maximum frequency
Actual signals and parameters 215
to 31
(LOAD FD
Frequency input
on page 135.
Frequency input
on page 135.
Def/FbEq
DEFAULT
SET).
0
1
AUTO
0
1
DEFAULT
0
1
0 Hz
1 = 1 Hz
1000 Hz
1 = 1 Hz